My House is More Humid Than Normal

by | Sep 19, 2020 | HVAC, Indoor Air Quality, Understanding your home | 0 comments

Tune up furnace

I recently was asked to look at a new development in the summer of a home we recently remodeled. The concern is that it is in the ‘mid to high ’80’s and the house is humid.

  • OUTSIDE HEAT mid to high ’90s
  • INSIDE SET TO: 73deg
  • UPON ARRIVAL: House is 70 deg AC not running. Fan in auto
  • Humidity inside 44%
  • Humidity outside 36%

Background information

The AC unit was replaced 4 years ago with a 3 ton coil (Inside) 2.5 ton compressor (Outside). We added 650SF to a 1500 SF home and a new furnace that was installed above the coil so it is a down draft forced air system. After further questioning, the client noticed the issue had just been in the last couple of weeks. Otherwise everything is working well through some over 100 degree days in a row.

My Hypothesis

The addition to the home is very well insulated and tight. The windows were all closed. The AC (which is a dehumidifier) was not running. I think that they have not been using the exhaust fans as much as they could have and the windows need to be opened occasionally to get some fresh air into the home. The AC has not been calling for cooling so it has not had a chance to decrease the humidity. We create a lot of humidity by living indoors, breathing, bathing, boiling , cooking, etc. If there s no way to get it out it will feel muggy in the home.

Recommendation:

  1. Use bathroom and cooking exhaust fans more.
  2. Open the windows at night.
  3. Air out the home.

My HVAC Buddy’s Hypothesis

For some reason in Idaho most homes have a mismatched coil and condensing unit. IMHO AC works best when the Coil and the compressor are rated the same tonnage. An undersized compressor runs longer and harder. If you have the correct match the compressor will run easier the coil will be colder and more humidity will come out of the air. Conventional wisdom says to pair the units.

MANUAL – J

In 1986 the ACCA Air Conditioning Contractors of America started recommending the size of Air conditioners. The felt that by imputing the load demands that they could right size the unit. HVAC contractors used to use their best judgement, overnight that became a thing of the past. Mechanical Engineers now have to plug all your homes vital statistics in and the correct size system will be pooped out in a Manual-J.

There is also a Manual-D for ducting. A Manual-S for equipment selection, and a Manual-T for air distribution that comes with the Manual-J.  HVAC contractors are obligated to follow the rules. Sometimes they get it wrong. Typically I see undersized units. Customer comfort and common sense need to play a part. Having a savvy Mechanical engineer and or a wise HVAC contractor can catch errors and nip them in the bud.

Results

I felt the overflow drain condensate tube, not much air was coming out of it. I blew on the condensation line which was a natural flow out of the home. It burbled for a moment then the water started to flow. Then I noticed that there was far more volume of air coming out of both the overflow and the “T” in the condensation line. We taped up the overflow with a piece of tape (with a slit in it) and the condensation line “T” completely so there would be more pressure helping the water to evacuate the home. The condensation line was not initially dripping but once I blew on it, the water started flowing again.


Your comments are welcome. To ask questions or get more information about fixing stuff, click here to email me directly, or call 208-639-1808

I do these things during non-Levco time to be sure it doesn’t interfere with the Remodeling business. Repairing things and understanding homes is just another passion of mine.

or visit our contact page.

Disclaimer: Some of these images came from the WEB. If they are yours, and you object to them being used, please claim them and I will gladly remove and replace them at once.

Related Posts

Sacramento Here We Come

Sacramento Here We Come

Lead Locators is proud to be participating in the Western Regional Lead and Healthy Housing Conference. This is a chance to stay abreast of developments in California, especially as they transition to taking over the RRP program. We will be introducing folks to...

read more

Leave A Comment

0 Comments

Submit a Comment

Your email address will not be published. Required fields are marked *

Yes, I would like to receive emails from Lead Locators. Sign me up!



By submitting this form, you are consenting to receive marketing emails from: Lead Locators. You can revoke your consent to receive emails at any time by using the SafeUnsubscribe® link, found at the bottom of every email. Emails are serviced by Constant Contact

Stay in touch

Sign up to stay in the know. We only share educational content and information. We don't believe in spam.


By submitting this form, you are consenting to receive marketing emails from: Lead Locators. You can revoke your consent to receive emails at any time by using the SafeUnsubscribe® link, found at the bottom of every email. Emails are serviced by Constant Contact

Recent Posts

Contractors Have No Need To Pre-Test For Lead Based Paint

Contractors Have No Need To Pre-Test For Lead Based Paint

As a contractor, I know that no testing is necessary in pre-1978 homes. Who cares? The EPA says that all homes built before 1978 were painted with lead-based paint. You don't need to test unless you want to exclude painted materials that don't contain lead. (A...

read more
Sacramento Here We Come

Sacramento Here We Come

Lead Locators is proud to be participating in the Western Regional Lead and Healthy Housing Conference. This is a chance to stay abreast of developments in California, especially as they transition to taking over the RRP program. We will be introducing folks to...

read more
Bringing Lead On Home To You

Bringing Lead On Home To You

Have you ever walked past a construction site where an old building was being demolished or renovated? You have likely brought some lead into your home. Have you ever gotten an old painted board or window upcycled into art?  You have likely brought some lead into your...

read more
The Circuitous Path To EPA Recognition

The Circuitous Path To EPA Recognition

Testing for Lead-based paint is easy and fun with the Lumetallix instant lead test kit. Although the 3M lead test swabs have been off the market since October 2023, we now know that 3M sold lead testing swabs to a company that will eventually reintroduce them to the...

read more